Fortress DBF501 Fire Curtain is designed to protect escape routes from the effects of fire, thus enabling building occupants to reach final exits. The fire curtain will protect the building contents by limiting the spread of fire and smoke while still allowing the passage of people or goods from one compartment to another.
Dimensions
Tailored specification to requirement.
Performance
Fire resistance: 2-hour fire resistance BS 476: Parts 20 & 22 (1987) and Parts 6 & 7 Class ‘O’.
CE-marked 01 May 2005.
See full specification for performance standards.
Curtain
BS 476 Fortress 240+ Fire Shield Fabric™ specially designed reinforced woven glass-fibre material coated on both sides with a reflective micronised aluminium polymer with an integrity rating of 120 minutes.
Guides
Fortress GCR-10 system™ 2mm/3mm galvanised steel guides with a fabric retaining track system that prevents the curtain from dislodging from the guide under heat exhaust and ventilation pressure.
Head Box
1.2mm galvanised steel 175mm x 175mm box assembly houses the curtain operator, barrel and curtain assembly.
Finish
Standard finish is galvanised steel bottom rail, guides and head box.
See full specification for options.
Operation
BS EN 12453 DBF501 Drive System™ 240 Volt single-phase in-barrel operator and 24 Volt activation system linked into the building fire alarm system. On receiving a signal from the fire alarm, the control panel will activate the drive-roller mechanism to lower the curtain under controlled descent to a pre-determined height.
In the event of power failure from a mains supply, we recommend that a Fortress FCPB™ Power Supply backup system is used.
NB: Control panel must be fitted to a 6amp/non-switched, fused, maintained essential supply.
Options and Accessories
See full specification for details.